Off Grid Kit

Off Grid Kit

Application of Labelling

SKU 0043

AS/NZS5033:2021

Clause 5.3.1.2

Warning Hazardous D.C. Voltage

Located inside the Ceiling or floor space adjacent to the access point and clearly visible.

Used when Disconnection points have been utilised and cables are run within the ceiling space / accessible floor space

SKU 0032

AS/NZS 5033:2021

Clause 5.4

PV DP Green Reflective Fire Sign

at least 100mm Dia

Located on or immediately adjacent to the main metering panel and main switchboard.

Visible to approaching emergency workers

SKU 0741

AS/NZ5033:2021

Clause 5.7

&

AS/NZ4777.1 2024

Shutdown Procedure

Placed adjacent to and visible from the equipment to be operated. “Inverter”

Where the inverter is adjacent to the switchboard it is directly connected to, the shutdown procedure may be placed within the switchboard.

Where a building has a fire panel, a sign shall be placed at the fire panel stating Multiple supplies with instructions as to the location of the IES Emergency shutdown procedure.

SKU 0159

AS/NZ5033:2021

Clause 5.7

&

AS/NZ4777.1 2024

Clause 6.2

Warning PV Array DC Isolators Do not De-Energize the PV array

Located under the Shutdown procedure

Where the energy source is not de-energised when the IES is shutdown. A warning shall be included in the emergency shutdown indicating that isolation of the energy source, by shutting down the inverter and isolating the IES , may not de-energise the energy source and further action may be required.

SKU 0596

AS/NZ4777.1 2024

Clause 6.3(g)

Warning Multiple Supplies Isolate all Supplies before working on this “Switchboard”

Located at the Switchboard the IES is directly connected.

SKU 0720

AS/NZ5033:2021

Clause 5.5.2.1

Warning Multiple DC Sources Turn off all D.C. isolators to isolate “Equipment”

Where multiple isolation/disconnection devices are used that are not ganged, this label will be fixed adjacent to the PCE “Power Consumption Equipment”

SKU 0724

AS/NZ4777.1 2024

Clause 6.8

Warning Multiple mode IES connected

Located on the Main switchboard, and all Distribution switchboards electrically connected between the main switchboard and a distribution switchboard where an IES is directly connected.

SKU 0752

AS/NZS5139:2019

Clauses 7.12.4

Warning Do not Disconnect under load

Disconnection for DVC-B & DCV-C systems

SKU 0022

AS/NZ5033:2021

Clause 5.3.2

Warning Hazardous DC Voltage

Located on any Array junction box containing PV DC Cable terminations.

Does not apply to PV array disconnecting devices as they have their own labelling requirements

SKU 0019

AS/NZ5033:2021

Clause 5.6.1.1

&

AS/NZ4777.1 2024

Clause 6.5

Solar Array on Roof

Located in switchboard

This label Is not specified in the latest standard, however still used by many,

Now a requirement if included with Solar System Layout. “Site map”

SKU 0363

AS/NZ5033:2021

Clause 5.5.2.2

Warning PV String Disconnection Point

Attached to the PV Module or structure within 300mm of every disconnection point to identify the location of the disconnection point

SKU 0035

Energy Safe Victoria – Institute of Electrical Inspectors.

Warning The Premise contains an electricity generation system

Located at the Fire indicator panel, Main switchboard and all Switchboards where an IES is directly connected.

SKU 0721

AS/NZ4777.1 2024

Clause 6.3 (b)

Main Switch (GRID)

Where the inverter is connected to the main switchboard, Fixed adjacent to the Main Switch grid supply

SKU 0722

AS/NZ4777.1 2024

Clause 6.3 (d)

Main Switch (INVERTER)

Fixed adjacent to the Main switch for the IES alternative supply

SKU 0723

AS/NZ4777.1 2024

Clause 6.3 (a)

Main Switch (SOLAR INVERTER)

where there is more than one IES Supplementary supply used to identify specific systems

SKU 0031

AS/NZ4777.1 2024

Clause 6.5

Inverter Location

Placed on the Switchboard where the inverter is not within 3 meters and fully visible from the main switchboard / and or fire panel

SKU 0716

AS/NZ5033:2021

Clause 5.5.2.2

Warning Loads must be isolated and circuits must be tested for the absence of current before unplugging.

Attached to both the Negative and Positive cable within 100mm  of the disconnection point of the PV String.

12

Cable Ties 150mm

Used to attached above labels

SKU 0029

AS/NZ5033:2021

Clause 5.5.1 & 5.5.2.1

PV Array D.C. Isolator

Attached to the D.C Isolator/s to the inverter/s

SKU 0030

AS/NZ4777.1 2024

Clause 6.6

Inverter A.C. Isolator

Attached to the A.C. Isolator adjacent the inverter/s

SKU 0743

AS/NZ4777.1 2024

Clause 6.2

Multiple Supplies IES Shutdown Procedure located in Main Switchboard

Located on the fire panel to show indicate the location of the shutdown procedure

2 options provided only one required

Other option below

SKU 0744

AS/NZ4777.1 2024

Clause 6.2

Multiple Supplies IES Shutdown Procedure located in ___________________

Located on the fire panel to show indicate the location of the shutdown procedure

2 options provided only one required

Other option above

SKU 0747

AS/NZ4777.1 2024

Clause 6.9

Warning Limited power output only available when grid power is interrupted

Located at the socket-outlet for the substitute supply from a multiple mode inverter

SKU 0735

AS/NZ4777.1 2024

Clause 6.4

Warning Multiple Supplies isolate inverter supply at Distribution board Location

Where the IES is directly connected to a distribution switchboard, sign shall be installed on the main switchboard and the distribution switchboard that the IES is connected.

SKU 0721

AS/NZ4777.1 2024

Clause 6.3 (c)

Main Isolator (GRID)

Where the inverter is connected to a distribution switchboard and where there is a main isolator/s for the distribution board it shall be labelled main isolator grid

This document is purely intended to provide a quick reference guide on where to apply labels.

Please refer to the regulatory requirements of the Distribution Network Service Providers and or Australian standards further detail.

It is the responsibility of the solar installer to ensure labelling meets all relevant requirements.