Inverter
This page provides information as to label requirements fror the for the home inverter system.
Category
Inverter
Location
Side of house
This page provides information as to label requirements fror the for the home inverter system.
Inverter
Side of house
The Standard required will depend on the type of design and/or installation.
| Standard | Title | Version Referenced |
| AS/NZS 3000 | Electrical Installations (known as the Wiring Rules) | 2018 Amendment 1&2 |
| AS/NZS 4777.1 | Grid connection of energy systems via inverters | 2024 |
| AS/NZS 5033 | Installation and safety requirements for photovoltaic (PV) arrays | 2021 |
| AS/NZS 5139 | Electrical installations – Safety of battery systems for use with power conversion equipment | 2019 |
SKU 0029
AS/NZS 5033:2021
Clause 5.5.2.1
PV ARRAY D.C. Isolator
All load break Disconnection devices shall be labelled with “PV ARRAY D.C. Isolators”
SKU 0721
AS/NZ5033:2021
Clause 5.5.2.1
Warning Multiple D.C. Sources turn off all D.C. isolators to isolate equipment
Where multiple isolation/disconnection devices are used that are not ganged, this sign shall be fixed adjacent to the PCE
SKU xxxx
AS/NZ5033:2021
Clause 6.6
Inverter
Inverter A.C, Placed on the inverter Isolator
SKU 0596
AS/NZ4777.1 2024
Clause 6.3(g)
Warning Multiple Supplies Isolate all Supplies before working on this “Switchboard”
Located at the Switchboard the IES is directly connected.