SKU 0043
AS/NZS5033:2021
Clause 5.3.1.2
Warning Hazardous D.C. Voltage
Located inside the Ceiling or floor space adjacent to the access point and clearly visible.
Used when Disconnection points have been utilised and cables are run within the ceiling space / accessible floor space
SKU 0032
AS/NZS 5033:2021
Clause 5.4
PV DP Green Reflective Fire Sign
at least 100mm Dia
Located on or immediately adjacent to the main metering panel and main switchboard.
Visible to approaching emergency workers
SKU 0741
AS/NZ5033:2021
Clause 5.7
&
AS/NZ4777.1 2024
Shutdown Procedure
Placed adjacent to and visible from the equipment to be operated. “Inverter”
Where the inverter is adjacent to the switchboard it is directly connected to, the shutdown procedure may be placed within the switchboard.
Where a building has a fire panel, a sign shall be placed at the fire panel stating Multiple supplies with instructions as to the location of the IES Emergency shutdown procedure.
SKU 0159
AS/NZ5033:2021
Clause 5.7
&
AS/NZ4777.1 2024
Clause 6.2
Warning PV Array DC Isolators Do not De-Energize the PV array
Located under the Shutdown procedure
Where the energy source is not de-energised when the IES is shutdown. A warning shall be included in the emergency shutdown indicating that isolation of the energy source, by shutting down the inverter and isolating the IES , may not de-energise the energy source and further action may be required.
SKU 0596
AS/NZ4777.1 2024
Clause 6.3(g)
Warning Multiple Supplies Isolate all Supplies before working on this “Switchboard”
Located at the Switchboard the IES is directly connected.
SKU 0720
AS/NZ5033:2021
Clause 5.5.2.1
Warning Multiple DC Sources Turn off all D.C. isolators to isolate “Equipment”
Where multiple isolation/disconnection devices are used that are not ganged, this label will be fixed adjacent to the PCE “Power Consumption Equipment”
SKU 0724
AS/NZ4777.1 2024
Clause 6.8
Warning Multiple mode IES connected
Located on the Main switchboard, and all Distribution switchboards electrically connected between the main switchboard and a distribution switchboard where an IES is directly connected.
SKU 0752
AS/NZS5139:2019
Clauses 7.12.4
Warning Do not Disconnect under load
Disconnection for DVC-B & DCV-C systems
SKU 0022
AS/NZ5033:2021
Clause 5.3.2
Warning Hazardous DC Voltage
Located on any Array junction box containing PV DC Cable terminations.
Does not apply to PV array disconnecting devices as they have their own labelling requirements
SKU 0019
AS/NZ5033:2021
Clause 5.6.1.1
&
AS/NZ4777.1 2024
Clause 6.5
Solar Array on Roof
Located in switchboard
This label Is not specified in the latest standard, however still used by many,
Now a requirement if included with Solar System Layout. “Site map”
SKU 0363
AS/NZ5033:2021
Clause 5.5.2.2
Warning PV String Disconnection Point
Attached to the PV Module or structure within 300mm of every disconnection point to identify the location of the disconnection point
SKU 0035
Energy Safe Victoria – Institute of Electrical Inspectors.
Warning The Premise contains an electricity generation system
Located at the Fire indicator panel, Main switchboard and all Switchboards where an IES is directly connected.
SKU 0721
AS/NZ4777.1 2024
Clause 6.3 (b)
Main Switch (GRID)
Where the inverter is connected to the main switchboard, Fixed adjacent to the Main Switch grid supply
SKU 0722
AS/NZ4777.1 2024
Clause 6.3 (d)
Main Switch (INVERTER)
Fixed adjacent to the Main switch for the IES alternative supply
SKU 0723
AS/NZ4777.1 2024
Clause 6.3 (a)
Main Switch (SOLAR INVERTER)
where there is more than one IES Supplementary supply used to identify specific systems
SKU 0031
AS/NZ4777.1 2024
Clause 6.5
Inverter Location
Placed on the Switchboard where the inverter is not within 3 meters and fully visible from the main switchboard / and or fire panel
SKU 0716
AS/NZ5033:2021
Clause 5.5.2.2
Warning Loads must be isolated and circuits must be tested for the absence of current before unplugging.
Attached to both the Negative and Positive cable within 100mm of the disconnection point of the PV String.
12
Cable Ties 150mm
Used to attached above labels
SKU 0029
AS/NZ5033:2021
Clause 5.5.1 & 5.5.2.1
PV Array D.C. Isolator
Attached to the D.C Isolator/s to the inverter/s
SKU 0030
AS/NZ4777.1 2024
Clause 6.6
Inverter A.C. Isolator
Attached to the A.C. Isolator adjacent the inverter/s
SKU 0743
AS/NZ4777.1 2024
Clause 6.2
Multiple Supplies IES Shutdown Procedure located in Main Switchboard
Located on the fire panel to show indicate the location of the shutdown procedure
2 options provided only one required
Other option below
SKU 0744
AS/NZ4777.1 2024
Clause 6.2
Multiple Supplies IES Shutdown Procedure located in ___________________
Located on the fire panel to show indicate the location of the shutdown procedure
2 options provided only one required
Other option above
SKU 0747
AS/NZ4777.1 2024
Clause 6.9
Warning Limited power output only available when grid power is interrupted
Located at the socket-outlet for the substitute supply from a multiple mode inverter
SKU 0735
AS/NZ4777.1 2024
Clause 6.4
Warning Multiple Supplies isolate inverter supply at Distribution board Location
Where the IES is directly connected to a distribution switchboard, sign shall be installed on the main switchboard and the distribution switchboard that the IES is connected.
SKU 0721
AS/NZ4777.1 2024
Clause 6.3 (c)
Main Isolator (GRID)
Where the inverter is connected to a distribution switchboard and where there is a main isolator/s for the distribution board it shall be labelled main isolator grid
This document is purely intended to provide a quick reference guide on where to apply labels.
Please refer to the regulatory requirements of the Distribution Network Service Providers and or Australian standards further detail.
It is the responsibility of the solar installer to ensure labelling meets all relevant requirements.